The voltage drop is calculated in accordance with the following equation:
,where:
- In, rated current [A],
- l, length of cable [m],
- σ, conductivity, for copper 58 [S*m / mm 2 ],
- Un, rated voltage [V],
- s, cable cross-section [mm 2 ],
Voltage drop on cables between generators and main switchboard is not to be more than 1%
Voltage drop is not to exceed:
- 10% for lighting and signalling devices,
- 10% for power consumers at short-time and intermittent service
- 7% for power and heating devices,
- 5% for navigation light circuit.